FSP Can Supply Hygood Inergen iFLOW Nitrogen Pilot Manual Actuator New and Replacement (30180APB) . The Actuator connects directly to the side of the pilot cylinder valve and is used to manually operate theiFLOW gas suppression system from the cylinder storage location.
The Local Manual Actuator can only be operated once the steel safety pin has been removed, which prevents accidental activation.
Activate by:
Remove the Safety Pin;
Pull the lever in the direction of the arrow embossed on the actuator body;
The operating pin will depress into the valve, and stay depressed until manually reset.
Hygood Inergen iFLOW New and Replacement Pilot Manual Actuator Technical Specifications and Information
Body: Brass
Safety pin: Steel
Lever: Brass
Swivel nut: Brass
Nominal stroke: 6 mm
Connection: M30 × 1.5 Female
Minimum / Nominal / Maximum
trigger pressure: Non applicable
Weight: 0.49 kg
Working temperature range: -20 °C to 50 °C
Testing of actuator: Possible
Overall size: 82 mm × 72 mm
Hygood Inergen iFLOW Pilot Manual Actuator New and Replacement Data Sheet
Ensure the Manual Actuator is reset correctly prior to installation onto the container, as incorrectly reset actuator will result in immediate operation of the pilot cylinder when installed, and a potentially hazourdous discharge of the container.