The Kidde Cylinder Supervisory Pressure Switch, P/N 06-118262-001, is intended to detect a fall in pressure in the Kidde Engineered System cylinder (see Figure 2-38). The cylinder supervisory pressure switch can be wired for either normally-open or normally-closed operation, depending on installation requirements. The cylinder supervisory pressure switch can be installed on 10 lb. through 350 lb. capacity Kidde Engineered System cylinders with a 2 in. discharge valve. If the pressure inside the cylinder falls below 305 PSIG (21 bar gauge), the switch contacts will transfer and invoke a “trouble†signal at the control panel.