Fike 80L IG-55 200bar or 300bar Cylinder with Valve with Exchange, refill and testing Proinert (CYL-80L-IG55-FIKE) is available to buy in increments of 1
FSP Can Supply Fike 80L IG-55 200bar or 300bar Cylinder Proinert with Valve Exchange, refill and testing (CYL-80L-IG55-FIKE IG71-200-55, IG71-300-55) steel, seamless gaseous fire suppression containers, filled with Inert Gas.
Each filled cylinder comes with an actuator and a ProInert Valve Assembly, which includes a combined pressure gauge and switch device to allow visual pressure indication and cylinder pressure monitoring by a fire control panel. Each cylinder can be mounted either upright or horizontally.
Fike 80L IG-55 200bar or 300bar Cylinder Exchange, refill and testing with Valve Technical Specifications and Information
Cyilnder Size:
80 Liter (water capacity)
Cylinder Height:
75 in (1910 mm)
Cylinder Width:
10.5 in (267 mm)
Mounting Position:
Upright
Cylinder Part Number:
IG71-103-200-55
IG71-103-300-55
Cylinder – Pressurization Level:
2900 psi at 60°F (200 bar at 15°C)
4351 psi at 60°F (300 bar at 15°C)
Cylinder Storage Temperature Limitation:
-4°F to +120°F (-20°C to +48°C) for cylinder and all related items
Agent Capacity:
572.3 ft3 (16.2 m3) @ 200 bar
801.6 ft3 (22.7 m3) @ 300 bar
Cylinder Rating:
DOT 3AA3000 (US Department of Transportation)
TC-3AAM (Transport Canada)
EN ISO 9809-2
Cylinder Actuation Methods:
Electric – UVO (Input from Control Panel)
Manual – Push button on UVO
Pneumatic - Relay Actuator or Pneumatic Actuator
Cylinder Color:
Signal Red
Tare Weight:
244 lbs. (110.7 kg) approximate
Gross Weight:
200 bar: 294.5 lbs. (133.5 kg) approximate
300 bar: 315 lbs (142.8 kg) approximate
Fike 80L IG-55 200bar or 300bar Cylinder with Valve Exchange, refill and testing Data Sheet
ARGONITE can be used to suppress fire in a diverse and challenging range of applications.
Data Processing
Data Centres, Computer Suites, Telecom Centres, Tape Storage Libraries, UPS Rooms, Financial Centres and Banks
Cleanrooms
Electronic equipment manufacturing, Medical and Laboratory Equipment, Biotechnology, Pharmaceutical and Medical Facilities, Operation Rooms, Universities and Colleges
Communications
Internet Service Providers, Switch Rooms, Control Centres, Cell Sites, Railway Signalling Centres, Air Traffic Management Centres, Military Installations
Heritage preservation
Art Galleries, Museums, Libraries, Classic Car Garages, Cultural Centres, Archive Stores
Power generation
Generators, Gas Turbines, Substations, Control Rooms
Oil & Gas
Offshore Oil and Gas Installations, Pipeline Pumping Stations, Petrochemical Plants