The Pneumatic Release can be used to release the stem of a spring loaded gas shut off valve
with a minimum operating pressure of 35 PSI (241 kPa). When a system discharges, pressure
on the piston within the Pneumatic Release causes the piston to move, thereby retracting a
normally protruding pin. The pin is used as a support for a cable linkage to:
? gas valve stem
? ventilation dampers
The 1/8-inch by 1-1/2-inch pipe nipple connects the Pneumatic Release to a 12-inch riser off
the agent distribution piping.
Retraction of the pin removes support for the linkage allowing it to pull away, thus releasing
the valve stem which now moves to the closed position under the force of the valve closing
spring.